Cycles of concentration, scale on heat exchangers, corrosion in closed loops and biofilm in cooling towers — a treatment programme, not a single drum of chemical.

A cooling system is a mass balance. Every kilogram of make-up water brings hardness and silica; evaporation concentrates it; bleed controls it. Chemicals then buy you a higher safe cycles-of-concentration figure, and the economics of the whole programme sit in that number.

Start with the balance

MeasurementDecides
Make-up hardness, alkalinity, silicaMaximum cycles before scaling
Conductivity, chlorideBleed control set point
LSI / RSIScaling or corrosion tendency
Corrosion rate (coupons or probes)Inhibitor performance
Microbiological counts, ATPBiocide programme
Delta-T on heat exchangersEarly fouling signal

Programme structure

  1. Scale control — phosphonate or polymer inhibitor, 2–10 ppm, dose proportional to make-up.
  2. Corrosion control — zinc, phosphonate, molybdate or azole combination, targeted at carbon steel and copper alloys.
  3. Dispersion — acrylic or phosphonate dispersant for iron, silica and hardness in suspension.
  4. Biocide — alternate oxidising and non-oxidising actives; shock dose with a defined holding time.
  5. RO and boiler — antiscalant, oxygen scavenger and membrane cleaners as separate programmes.

Common failure modes

  • Scaling at the designed cycles — the water changed seasonally and the inhibitor dose did not.
  • Corrosion after a biocide change — biofilm removal exposes bare metal; adjust inhibitor first.
  • Legionella risk in a cooling tower — biocide alone is not a control plan; drift, aerosol and maintenance matter.
  • RO flux decline — antiscalant underdose, or a cleaner applied at the wrong pH for the foulant.

Send the make-up analysis, cycles, system volume and current programme. We propose a dosing scheme and a monitoring plan.

Questions buyers ask

Direct answers

How many cycles of concentration can we run?

It depends on the limiting parameter: silica, hardness or alkalinity. The safe figure is calculated from the make-up analysis plus the inhibitor's capability, then confirmed by monitoring.

Which biocide for a cooling tower?

Alternating oxidising and non-oxidising actives, because a single biocide selects resistant biofilm. Dose, holding time and frequency matter as much as the active choice.

Do we need a corrosion inhibitor if the water is soft?

Soft water is often corrosive, not safe. Low hardness and low alkalinity push the water toward corrosion; the LSI will tell you which side you are on.

Can you supply RO antiscalant and cleaners together?

Yes: antiscalant for the feed, plus alkaline, acid and chelating cleaners. The cleaner must match the foulant, so keep the last cleaning record.

Send your water or material data.

We reply with a product route, indicative dosage and the documents you need.

Contact technical sales ↗