A cooling system is a mass balance. Every kilogram of make-up water brings hardness and silica; evaporation concentrates it; bleed controls it. Chemicals then buy you a higher safe cycles-of-concentration figure, and the economics of the whole programme sit in that number.
Start with the balance
| Measurement | Decides |
|---|---|
| Make-up hardness, alkalinity, silica | Maximum cycles before scaling |
| Conductivity, chloride | Bleed control set point |
| LSI / RSI | Scaling or corrosion tendency |
| Corrosion rate (coupons or probes) | Inhibitor performance |
| Microbiological counts, ATP | Biocide programme |
| Delta-T on heat exchangers | Early fouling signal |
Programme structure
- Scale control — phosphonate or polymer inhibitor, 2–10 ppm, dose proportional to make-up.
- Corrosion control — zinc, phosphonate, molybdate or azole combination, targeted at carbon steel and copper alloys.
- Dispersion — acrylic or phosphonate dispersant for iron, silica and hardness in suspension.
- Biocide — alternate oxidising and non-oxidising actives; shock dose with a defined holding time.
- RO and boiler — antiscalant, oxygen scavenger and membrane cleaners as separate programmes.
Common failure modes
- Scaling at the designed cycles — the water changed seasonally and the inhibitor dose did not.
- Corrosion after a biocide change — biofilm removal exposes bare metal; adjust inhibitor first.
- Legionella risk in a cooling tower — biocide alone is not a control plan; drift, aerosol and maintenance matter.
- RO flux decline — antiscalant underdose, or a cleaner applied at the wrong pH for the foulant.
Send the make-up analysis, cycles, system volume and current programme. We propose a dosing scheme and a monitoring plan.