Quick answer: PAC is a pre-hydrolysed aluminium coagulant, normally dosed at 20–150 ppm of product (5–40 ppm as Al2O3), with an optimum pH of about 6.0–8.0. Higher Al2O3 and basicity mean less inert salt per tonne; the dose that matters is the one found by jar test on your own water.
What PAC does
PAC supplies partially hydrolysed aluminium species that neutralise colloidal charge and form a hydroxide floc that sweep-removes turbidity, colour, some COD and phosphate. Because it is already partly hydrolysed, it reacts faster and consumes less alkalinity than aluminium sulfate, and it works over a wider pH band.
| Compared with | PAC advantage | PAC limitation |
|---|---|---|
| Aluminium sulfate | Less alkalinity consumption, faster floc, wider pH | Higher price per tonne of product |
| Ferric chloride | No chloride load, no strong colour | Lower phosphorus removal per mole of metal |
| PFS | Lower iron residual, no staining in some uses | Less effective for colour and sulphide in some waters |
Read the specification correctly
| Parameter | What it means | What to watch |
|---|---|---|
| Al2O3 content | Active coagulant per tonne | 26%, 28% and 30% differ by roughly 15% in active content — compare cost per kg Al2O3, not per tonne |
| Basicity | Degree of pre-hydrolysis, 40–85% | Higher basicity = less alkali demand and less pH drop, but can be less stable in storage |
| pH of 1% solution | 3.5–5.0 typical | Very low pH signals strong acidity and a bigger alkalinity hit |
| Insolubles | Inert residue | High insolubles mean sludge and blocked dosing lines |
| Heavy metals | Potable-water compliance | Required for drinking-water grade; ask for the COA |
A "30% PAC" at a low basicity can perform worse than a 28% at high basicity in soft water, because the plant then pays for alkali as well.
Setting the dose
- Run a jar test at the plant's actual pH, not at the pH you wish you had.
- Use a dose series: 10, 20, 40, 60, 80, 100 ppm as product.
- Rapid mix 60 seconds at high energy, then slow mix 15 minutes.
- Let settle 20–30 minutes; measure turbidity, pH and, if relevant, phosphate.
- Choose the lowest dose where turbidity stops improving — beyond that, you are buying sludge, not clarity.
Typical results: surface water 10–40 ppm; municipal secondary effluent 20–60 ppm; industrial effluent 40–150 ppm; phosphorus-driven dosing often 1.5–3 moles Al per mole P.
The pH window
The optimum is 6.0–8.0 for PAC, narrower for low-alkalinity water. Two failure patterns:
- pH below 5.5 — the floc does not form properly and residual aluminium rises.
- pH above 8.5 — aluminate formation, poor floc, high aluminium residual.
Check alkalinity before increasing dose. If alkalinity is below about 40 mg/L as CaCO3, a coagulant will drive pH down and the plant will chase its own tail.
When PFS is better
Polyferric sulfate suits colour removal, sulphide-bearing water, cold water and cases where a denser floc is wanted. Iron residual and staining are the trade-offs. In potable water, check the iron limit in the local standard before switching.
Common mistakes
- Comparing products per tonne instead of per kg Al2O3.
- Increasing the dose when the real issue is mixing energy or pH.
- Using a potable grade specification for an industrial application, which raises cost with no benefit.
- Storing liquid PAC in heat and sunlight; stability drops and dosing lines clog.
Send pH, alkalinity, turbidity or SS, and phosphate. We return a grade, a dose band and the jar-test sheet you can run in the plant laboratory.